v = 0.5 – 1.0 m/s
Wavy Free Surface Flow
At low rainfall intensity (< 15% design load), water enters the outlet without engaging the baffle. System behaves like conventional open-channel gravity drainage.
HYDRAULIC FLOW BENCHMARKS
Explore negative pressure priming mechanics, two-phase transient transitions, and full-bore hydraulic performance compared with gravity systems.
Conventional Gravity vs. Siphonet Full-Bore System
From initial sheet flow to steady-state full-bore depressurization under design rainfall load.
v = 0.5 – 1.0 m/s
At low rainfall intensity (< 15% design load), water enters the outlet without engaging the baffle. System behaves like conventional open-channel gravity drainage.
v = 1.0 – 1.8 m/s
As roof ponding approaches 25–35 mm, wave crests seal the pipe crown. Air pockets are trapped and accelerated down the collector creating rhythmic hydraulic surges.
v = 1.8 – 2.8 m/s
Air is entrained into micro-bubbles dispersed homogenously within the turbulent liquid phase. Continuous negative pressure builds at high-level junction elbows.
v = 2.8 – 6.0 m/s
Zero air entry. Hydraulic gradient utilizes full vertical building fall H to pull water at high velocity (up to 6.0 m/s), self-cleansing all piping and purging sediment.
Every EN 12056-3 siphonic installation integrates four precision-matched engineering groups operating under full-bore negative pressure.

Engineered air-blocker baffle disc prevents swirling air cores at 35–55 mm roof ponding depth, triggering instant full-bore priming.
Inspect specs
Seamless electrofusion PE100 HDPE headers (DN50–DN315) routed tightly horizontally beneath steel trusses with zero floor intrusion.
Inspect specs
Hot-dip galvanized 41x41mm steel channels isolating linear HDPE thermal movement while locking transient priming thrusts.
Inspect specs
Decelerates 3–5 m/s pressurized riser columns safely back into open-channel atmospheric flow before municipal sewer or cistern intake.
Inspect specsSiphonic systems require rigorous hydraulic balance: total head loss from every outlet to discharge must equal the available geometric height within 10 kPa residual tolerance.