1. The Core Siphonic Rainwater Discharge Equation
Accurate determination of peak rainwater flow rate is the mathematical foundation of every Siphonet siphonic drainage system. Under-calculating flow rates risks roof ponding and structural overload during tropical cloudbursts, while arbitrary over-sizing prevents pipes from reaching full-bore priming velocity. In accordance with EN 12056-3, the design flow rate Q (in liters per second, l/s) is calculated by:
Q = r × A × c1 × c2
- r — Design rainfall intensity, expressed in l/(s·m2). Note the conversion:
1 mm/h = 0.0002778 l/(s·m2), so a tropical monsoon storm of180 mm/hequals0.050 l/(s·m2). - A — Effective horizontal catchment area of the roof exposed to rainwater, in m2.
- c1 — Runoff coefficient (dimensionless, typically 0.3 to 1.0), determined by roof surface material and water retention characteristics.
- c2 — Risk coefficient (dimensionless, from 1.0 to 3.0), applied when reliable local statistical rainfall intensity data is unavailable or when building occupancy demands heightened flood protection.
2. Determining Effective Roof Area (A) and Runoff Coefficient (c1)
For pitched or flat roofs without adjacent taller structures, the effective catchment area equals the horizontal plan projection of the roof. However, when a tall vertical facade wall borders a lower roof terrace, wind-driven rain strikes the wall and cascades onto the lower roof; EN 12056-3 requires adding 50% of the exposed vertical wall area to the lower roof's catchment area.
The runoff coefficient c1 reflects surface impermeability:
- c1 = 1.0: Impervious metal standing-seam roofs, trapezoidal corrugated steel decks, concrete slabs with bituminous/PVC/TPO waterproofing membranes, and glass skylights.
- c1 = 0.8: Flat roofs covered with a thick gravel ballast layer.
- c1 = 0.5 – 0.6: Extensive green roofs (sedum/grass substrate depth < 100 mm).
- c1 = 0.3 – 0.4: Intensive landscaped roof gardens (soil depth > 100 mm).
3. Risk Coefficient (c2) Selection Matrix
When designing facilities in regions lacking dense meteorological return-period curves — or for high-value industrial and civic assets — the risk factor c2 provides a standardized safety multiplier:
| Roof Gutter Configuration & Building Risk Situation | Coefficient c2 |
|---|---|
| Standard external eaves gutters (overflow spills harmlessly outside the building envelope) | 1.0 |
| Eaves gutters where overflowing would cause particular inconvenience (e.g., over public building entrances or loading docks) | 1.5 |
| Non-eave gutters (internal valley/box gutters, parapet roofs) and all circumstances where abnormally heavy rain or blockage could cause water spillover inside the building | 2.0 |
| Non-eave gutters in buildings requiring an exceptional degree of protection (hospitals, theatres, telecommunications/data centers, hazardous chemical storage, museums, semiconductor fabs) | 3.0 |
4. Practical Worked Example for an Industrial Factory
Consider a 10,000 m2 standing-seam metal warehouse roof with an internal valley box gutter (non-eave gutter) located in a region with base rainfall intensity r = 0.042 l/(s·m2) (~151 mm/h). With c1 = 1.0 and c2 = 2.0 (for non-eave internal gutter protection), the design capacity across primary + emergency systems is Q = 0.042 × 10,000 × 1.0 × 2.0 = 840 l/s. Siphonet engineers split this load cleanly between the primary siphonic network (designed for 100% base storm) and an independent emergency siphonic overflow network so the factory remains completely dry even under extreme monsoon events.